Jade, Nagaraja and Balide, Venkatesham
(2018)
Study on Effect of Joints on the Modal Parameters
of Rectangular Duct.
International Journal of Acoustics and Vibrations, 23 (4).
pp. 547-556.
ISSN 1027-5851
Full text not available from this repository.
(
Request a copy)
Abstract
A duct is an enclosed passage for transmission of a substance, especially liquid or gas with extensive usage in heating, ventilation, and air conditioning (HVAC) applications and gas industries. Practically, duct shapes have deviations from ideal geometric shapes, predominantly in thin-walled structures due to joint conditions. The aim of the present research is to understand the effect of duct joints on modal parameters. In this study, Experimental Modal Analysis (EMA) is carried out on three different rectangular ducts having different joints and materials. Numerical Modal Analysis (NMA) is then performed on these ducts by modelling the corresponding joints. The Modal Assurance Criteria (MAC), frequency comparison, and auto-MAC plots are used to check the correlation between the experimental and numerical results. Based on these comparisons, a good match in natural frequencies but a mismatch in mode shapes are observed.
Actions (login required)
|
View Item |